N2XS(FL)2Y 20.3/35 kV TSEK |
Structure
|
Technıcal Data Maximum operating temp.:90°C Max.short circuit temp.:250°C (+≥ 5 sn) Installation temp.min:-20 °C Standarts: TS IEC 60502-2 VDE 0276 |
Applıcatıons They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high such as urban and industrial areas fed by electrical energy. If cable gets water inside due to the mechanical damages, swellable tapes prevent the movement of the water. |
Teknik Özellikler / Technical Features |
||||||||
Normal Kesit |
Kablo Dış Çapı |
Akım Taşıma Kapasitesi |
Çalışma İndüktansı |
Çalışma Kapasitesi |
İletken DC Direnci (20 oC) |
Net Ağırlık |
Sevk Uzunluğu |
|
Rated Cross Section |
Overall Diameter Of Cable |
Current Carrying Capacity |
Operating Inductance |
Operating Capacity |
Conductor DC Resistance at (20 oC) |
Net Weight |
Delivery Length |
|
mm2 |
mm |
Air (A) |
Ground (A) |
mH / Km |
µF / km |
Ohm / Km |
Kg / Km |
Mt |
1x35/16 |
36.00 |
169 |
165 |
0,69 |
0,12 |
0,524 |
1230 |
1000 |
1x50/16 |
37.20 |
249 |
232 |
0,66 |
0,13 |
0,387 |
1430 |
1000 |
1x70/16 |
39.20 |
308 |
284 |
0,63 |
0,14 |
0,268 |
1680 |
1000 |
1x95/16 |
40.80 |
375 |
339 |
0,30 |
0,15 |
0,193 |
1980 |
1000 |
1x120/16 |
42.60 |
430 |
385 |
0,59 |
0,17 |
0,153 |
2300 |
1000 |
1x150/25 |
43.80 |
485 |
430 |
0,57 |
0,18 |
0,124 |
2740 |
1000 |
1x185/25 |
45.80 |
554 |
484 |
0,55 |
0,19 |
0,0991 |
3100 |
1000 |
1x240/25 |
48.20 |
653 |
559 |
0,53 |
0,21 |
0,0754 |
3640 |
1000 |
1x300/25 |
50.20 |
739 |
627 |
0,51 |
0,23 |
0,0601 |
4450 |
1000 |
1x400/35 |
54.20 |
842 |
701 |
0,49 |
0,25 |
0,0470 |
5400 |
500 |
1x500/35 |
57.20 |
965 |
786 |
0,48 |
0,27 |
0,0366 |
6500 |
500 |
1x630/35 |
62.20 |
1096 |
875 |
0,46 |
0,30 |
0,0283 |
7850 |
500 |