N2XS(FL)2Y 26/45-47 kV TS 10382 IEC 60840 |
Structure
|
Technıcal Data Permissible operating temp.: 90°C Max. short circuit temp.: 250°C (+≤ 5 sec.) Installation temp. min: -20°C |
Applıcatıons These cables used in energy networks with sudden load changes laid in residentail or industrial areas, underground or in ducts. If the cables gets water inside due to the mechanical damages swellable tapes prevent the water. |
Teknik Özellikler / Technical Features |
||||||||
Normal Kesit |
Kablo Dış Çapı |
Akım Taşıma Kapasitesi |
Çalışma İndüktansı |
Çalışma Kapasitesi |
İletken DC Direnci (20 oC) |
Net Ağırlık |
Sevk Uzunluğu |
|
Rated Cross Section |
Overall Diameter Of Cable |
Current Carrying Capacity |
Operating Inductance |
Operating Capacity |
Conductor DC Resistance at (20 oC) |
Net Weight |
Delivery Length |
|
mm2 |
mm |
Havada 30 oC Air 30 oC (A) |
Toprakta 20 oC Ground 20 oC (A) |
mH / Km |
µF / km |
Ohm / Km |
Kg / Km |
Mt |
1x70/16 |
41,60 |
347 |
304 |
0,478 |
0,108 |
0,2680 |
1970 |
1000 |
1x95/16 |
43,40 |
420 |
360 |
0,453 |
0,119 |
0,1930 |
2280 |
1000 |
1x120/16 |
44,80 |
483 |
408 |
0,436 |
0,128 |
0,1530 |
2570 |
1000 |
1x150/25 |
46,20 |
540 |
445 |
0,422 |
0,137 |
0,1240 |
2970 |
1000 |
1x185/25 |
48,00 |
614 |
498 |
0,406 |
0,148 |
0,0991 |
3360 |
1000 |
1x240/25 |
50,30 |
718 |
569 |
0,389 |
0,162 |
0,0754 |
3970 |
1000 |
1x300/25 |
52,60 |
813 |
633 |
0,374 |
0,176 |
0,0601 |
4600 |
500 |
1x400/35 |
55,70 |
904 |
686 |
0,358 |
0,195 |
0,0470 |
5630 |
500 |